KIC45-100(NC) MCCB
Be applicable to circuit with rated voltage 230V/400V, rated frequency 50Hz/60Hz and rated current not exceeding 125A. Protection and control of circuit against overload and short circuits in commercial and household installation.
Standard↓
GB14048.2
IEC60947.2
Main technical parameters
Type |
KIC45-(NC100H) |
Number of poles |
1P,2P,3P ,4P |
Rated Current(In) |
63,80,100,125A |
Rated Voltage(Un) |
AC 230/400V |
Rated frequency |
50(60)Hz |
Curve |
C,D |
Short-circuit breaking capacity(Icn) |
10000A |
Power factor(Cos¢) |
1P,2P,3P,4P:0.45~0.50 |
2P,3P,4P:0.20~0.25 |
Endurance |
≥ 20000 |
Terminal protection |
IP20 |
|
|
|
|
Circumstance temperature -5°C ~ +40°C, average temperature not exceeding 35°C.
·Altitude above sea level less than 2000 m.
·Humidity not exceeding 50% at 40°C and not exceeding 90% at 25°C.
·Installation class II or III.
·Pollution class 2.
·Installation method DIN Rail mounting type.
·The external magnetism shall not be more than 5 times of terrestrial one.
·Product shall be installed vertically at the place where there shall be no severe impact and vibration. The product is switched on when the handle is at upper position.